ARMAN ENERJİ

Solid Insulated Vacuum Recloser

The Solid Insulated Vacuum Recloser is designed for the inherently reliable, intelligent automation and environmentally friendly, completely oil free and gas free. the mechanism is enclosed in a powder coated stainless steel and Hydrophobic cycloaliphatic epoxy resin bushing is bolted on to the stainless steel enclosure. The Hydrophobic cycloaliphatic epoxy advantages are permanent flexibility, superior surface arc tracking resistance, hydrophobic preventing continuous track from forming leakage current paths, ultraviolet resistance and high tensile strength. The control cubicle is heat insulated with polyurethane to minimize temperature variation and protected from solar heating as adopting sunshine cover to the outside and heat insulation inside of control cubicle.
 

Item

Rating

 

 

Item

Rating

Rated Voltage (kV)

15/27/38

 

 

Basic Impulse Withstand Voltage (kV 1.2x50)

110/150/170

Rated Current (A)

630/800

 

 

Control Cubicle Operation Voltage

AC 220V 1 Phase

Frequency

50/60

 

 

Control Cubicle Control Power

DC 24V

Short circuit interrupting Current (kA)

12.5/16(R.M.S.)

 

 

Control Cubicle Permeable Voltage

85-110%

Making Current Capacity (kA)

32.5/40 (Peak)

 

 

Control Cubicle Power Frequency Withstand Voltage

2kV 1 min.

Opening Time (Cycle)

≤3.0(0.05sec)

 

 

Control Cubicle Basic Impulse Withstand Voltage (kV 1.2x50)

6kV, 3kA

Closing Time (Cycle)

≤5(0.1sec)

 

 

Weight (kg) Tank

121/145/175

Power Frequency  Withstand Voltage (kV)

Dry:50/60/70
Wet:45/50/60

 

 

Weight (kg) Control Cubicle

65/80

Communication Port

RS232,RS485/422, RJ 45, Fiber optic / Bluetooth (Option)

 

 

 

 

 
Key Characteristics
 

  • The first Independent Technology in Korea and certified by KEMA Type Test
  • No gas pressure switch / release device / refilling valve
  • Gas free, Oil free
  • IEC Std, Heavy polluted area application Bushing
  • Interrupter : 10,000 times of operation
  • Mechanism : 10,000 times of operation
  • Eliminating Tank explosion cause from internal arc
  • International Standard: IEEE/ANSI 37.60, IEC 62271-111 fully complied